# Values for the cooler of the FT-817 radio. flags: USE_DCDC_CONTROL: true config: # temperature corridor definition CORRIDOR_MIN_TEMPERATURE: 28.0 CORRIDOR_MAX_TEMPERATURE: 32.0 # The fan is started when temperature rises above this temperature. FAN_START_TEMPERATURE: 30.0 # The fan is stopped when the temperature falls below this point. FAN_OFF_TEMPERATURE: 25.0 # Emergency temperature level. If this is reached, the duty cycle is directly # set to the maximum to skip a long ramp-up phase. EMERGENCY_TEMPERATURE: 40.0 # The fan PWM duty cycle cannot fall below this limit. It is held until # temperature falls below the off-temperature. DUTY_CYCLE_MIN: 25.0 # The fan PWM duty cycle cannot go above this limit. Should be set to 100. DUTY_CYCLE_MAX: 100.0 # The fan is always started with this duty cycle. Do not set too low. DUTY_CYCLE_START: 60.0 # gain unit: percent duty cycle change per °C deviation per update cycle (100 ms) GAIN_T_HIGH_P: 2.000 GAIN_T_HIGH_I: 0.125 GAIN_T_LOW_P: 0.000 GAIN_T_LOW_I: 0.125